OUR COMPUTER EXCHANGES: CX1
 
 
Building
Building area : Gross - 7,600m² (81,000 ft²)
  : Data Center - 4,300m² (45,500 ft²)
Floor Loading : 7.5kN/m² in data center area
Clear Height : 4.59m (concrete floor to ceiling)
Raised floor : 1.00m
Column Grid : 9.00m
Passenger Lift : 2 nos. 1.6 ton lifts - 1.5 m width x 2.4m depth x 2.4m height
Goods life : 1 no. 3.0 ton lifts - 2.8m width x 3.2m depth x 2.4m height
Car parks : 99 spaces
Insulation : Brick wall with mineral wool and gypsum board insulation
Roof : Double layer concrete roof slab to prevent water leakage

Building Management
Operations : 24 x 7 facilities management team at site
EMS : Temperature and humidity monitoring
  : M & E Operations and Power monitoring

Cooling
Temperature : 18 C to 24 C
Humidity : 35% to 65% RH
Cooling : Air Cooled System
Resilience : N+1
Fire Detection and Suppression
Detection : High sensitivity smoke detectors (HSSD)
  : Addressable heat and smoke detectors
Suppression : Water mist system in data center and common area
  : Gas system in mechanical and electrical area
Telecommunications
Carrier : Access to multiple telecommunications provider via (MMR)
MDF : 2 rooms
MMR : 1 rooms
Satellite : Roof space available for satellite and antenna equipment

Power
Mains Power : 2 x 11kV incomers from 2 sources
Redundancy : N+1 option
Distribution : 415V busbar system
Transformers : Up to 12MVA cast resin transformers
Generators : Up to 12MVA diesel generators
Fuel Storage : 30 hours support at full load
Fuel Delivery : 4 hours response
UPS : N+1 option with minimum 10 minutes backup
Security
Presence : 24 x 7 security team
Personnel : Proximity card readers, upgradeable to biometric
Vehicle : Barrier control
Delivery : Managed by security personnel
CCTV : Multiple CCTV cameras with offsite archival